KLD-BMS2000 Series

              High Performance Harmonic Protector

              Filtering harmonic frequency and energy, efficiently controlling harmonic interference, eliminating harmonics at the source.

              PRODUCT OVERVIEW

              Ideal power supply should be a sinusoidal waveform with a single constant frequency and specified amplitude. When a sinusoidal voltage is applied to a non-linear load, the current will be distorted into a non-sinusoidal waveform, which leads to a voltage drop in the grid impedance, making the voltage waveform turn to be non-sinusoidal as well. Applying Fourier series decomposition to non-sinusoidal waveforms, in which the component with the same frequency as the industrial frequency is called the fundamental wave, and the component with a frequency greater than the industrial frequency is called the harmonic wave.

              KLD-BMS2000 series high-performance harmonic protector eliminates harmonics at the power side through digital logics and detects the current waveform generated by non-linear loads in the power grid in real time. It decomposes and reverses the harmonic wave, and then injects the reversed current into the power grid by triggering IGBT inverter to filter out the harmonics. It is mainly applied to the control of harmonics at the power side to protect the important power equipment of customers.

              COMPREHENSIVE HARMONIC
              CONTROL CAPABILITY

              KLD-BMS2000 series high-performance harmonic protector dynamically analyzes system harmonics in real time and filters them out to purify the system, and the response speed is very fast.

              It automatically controls the harmonics according to the situation, and can filter out a wide range of harmonics, including 2nd to 71st harmonics. It can filter out the harmonics of phase A, B and C respectively, and the neutral line has the filtering capacity three times stronger than others, featuring comprehensive high-performance harmonic control.

              MODULAR DESIGN

              KLD-BMS series high-performance harmonic protector adopts modular design with intelligent duct design, featuring lower loss and more convenient application.

              It has complex model structure, wall-mounted and rack-mounted models are all designed in modules. Its compact space design and accurate capacity control can fully meet the needs of different customers, and applicable to a wide range of fields, making it very convenient in the transportation process, capacity increase and maintenance at the later stage. Also, the modular design is easier to be integrated into the power distribution cabinet.

              Technical Parameters

              System voltage 110V~690V
              Rated frequency 50Hz/60Hz(±5%)
              Filter range 2nd-71st harmonics, the order and times of harmonics can be specified
              Response time Transient response time response time≤100ms,F(xiàn)ull response time≤10ms
              Filter effect As high≥97%
              Communication protocol Modbus protocol, RS485/232 module
              Module design Multiple pcs in parallel
              PF adjustment Adjust PF from inductive 0.6 to capacitive 0.6
              Switch frequency 20kHz
              Balance protection Programmable phase balance protection
              Power consumption ≤3% of its power consumption
              Protection degree IP21, high protection kit can be added
              Altitude Conventional 2000 meters, higher altitude can be customized
              Relative humidity ≤95%RH(no condensing)
              Temperature range -40℃~+65℃
              Selection table

              Model Rated Compensation Current(A) Rated voltage(V) Installation method Cooling method
              KLD-BMS2000-50A-400V 50 400 Wall-mounted or rack-mounted Forced air-cooling
              KLD-BMS2000-100A-400V 100 400 Wall-mounted or rack-mounted Forced air-cooling
              KLD-BMS2000-150A-400V 150 400 Wall-mounted or rack-mounted Forced air-cooling
              KLD-BMS2000-200A-400V 200 400 Wall-mounted or rack-mounted Forced air-cooling

              Technical Parameters


              • System voltage:110V~690V

                Rated frequency:50Hz/60Hz(±5%)

                Filtering range:2nd-71st harmonics, the order and times of harmonics can be specified

                Response time:Transient response time response time≤100ms,F(xiàn)ull response time≤10ms

                Filter effect:As high≥97%

                Communication protocol:Modbus protocol, RS485/232 module

                Module design:Multiple pcs in parallel

                PF adjustment:Adjust PF from inductive 0.6 to capacitive 0.6

                Switch frequency:20kHz

                Balance protection:Programmable phase balance protection

                Power consumption:≤3% of its power consumption

                Protection degree:IP21, high protection kit can be added

                Altitude:Conventional 2000 meters, higher altitude can be customized

                Relative humidity:≤95%RH(no condensing)

                Temperature range:-40℃~+65℃

              Selection table


              • KLD-BMS2000-50A-400V

                Rated Compensation Current(A):50

                Rated voltage(V):400

                Installation method:Wall-mounted or rack-mounted

                Cooling method:Forced air-cooling

                KLD-BMS2000-100A-400V

                Rated Compensation Current(A):100

                Rated voltage(V):400

                Installation method:Wall-mounted or rack-mounted

                Cooling method:Forced air-cooling

                KLD-BMS2000-150A-400V

                Rated Compensation Current(A):150

                Rated voltage(V):400

                Installation method:Wall-mounted or rack-mounted

                Cooling method:Forced air-cooling

                KLD-BMS2000-200A-400V

                Rated Compensation Current(A):200

                Rated voltage(V):400

                Installation method:Wall-mounted or rack-mounted

                Cooling method:Forced air-cooling