KLD-DVR Series

              Dynamic Voltage Regulation Real-time Control Equipment

              It’s an off-line short duration energy compensation solution. When voltage dips and other issues occur, it can quickly support the load without power outage during switching to ensure the integrity of the supply voltage.

              PRODUCT OVERVIEW

              With the rapid development of the modern electric power industry and the transformation in the structure of electricity loads in the system, social production and precision manufacturing are growingly dependent on electronic equipment. Voltage dips have become a major problem for users.

              According to the data of EPRI, more than 92% of power quality events are voltage dips and swells, while other power quality events only account for less than 8%. Voltage dips have been identified as the most prevalent event in power systems by a number of international research organizations. Therefore, it is vital to protect the sensitive equipment from voltage dips (swells). KLD-DVR series dynamic voltage regulation real-time control equipment provides the solution of voltage dips (swells) equipment, which can quickly correct the voltage in real time and solve the problem of voltage dips, swells and interruptions in the power supply of social production or precision manufacturing, ensuring that the loads continue to operate and the power supply will not be interrupted.

              VOLTAGE DIP

              The definition of voltage dips is specified in IEEE standard and national standards "Power quality—Voltage dips and short interruptions": a phenomenon that the effective power frequency voltage of a point in the power system is temporarily reduced to 10% ~ 90% of the rated voltage, and lasts for 10ms ~ 1min, during which the system frequency remains the nominal value and then returns to normal level.

              OPERATION MODE INTRODUCTION

              Grid voltage is in normal operation

              KLD-DVR is in grid power supply mode, where the grid supplies power directly to the load through the equipment, while the KLD-DVR converter obtains energy from the output side to charge the supercapacitor.

              Grid voltage dips

              KLD-DVR is in inverter power supply mode, where the energy from the supercapacitor is converted by the KLD-DVR converter into a standard voltage source to power the load.

              Grid voltage powers off

              KLD-DVR is in inverter power supply mode, where the energy from the supercapacitor is converted by the KLD-DVR converter into a standard voltage source to power the load.

              FAST COMPENSATION EFFECT

              KLD-DVR series can provide fast and accurate protection for the user's important equipment, preventing voltage dips and swells from causing equipment shutdown and economic losses. Even if the voltage drops to zero, the equipment can still output 100% of the rated voltage to support the normal operation. The typical response time is less than 2ms.

              Technical Parameters

              Input
              Rated AC input voltage 208V-480V(other voltage levels can be customized)
              Input Voltage range -15%~+15%
              Grid frequency range 50Hz/60Hz±5Hz
              Wiring mode Three-phase three-wire/three-phase four-wire
              Multiple pcs in parallel Support multi-module parallel connection
              Operating efficiency >99%
              Output
              Compensation capability 0-100% for standard model, 100% for remaining models
              OutputFrequency 50±0.01Hz or 60±0.01Hz
              Voltage harmonic ≤3%
              Voltage imbalance (negative sequence/ positive sequence) <3% for 100% unbalanced loads
              Overload capacity 200%
              Performance indicators
              Fast response time <10us
              Full response time <2ms
              Noise ≤60db(100% load)
              Heat dissipation mode Intelligent air cooling
              Protection functions Short-circuit protection, DC busbar undervoltage/overvoltage protection, power semiconductor fault protection, overload protection, etc.
              Application environment
              Ambient temperature -10℃~+50℃
              EnvironmentHumidity Maximum 95%RH (no condensing)
              Storage temperature -25℃~55℃
              Altitude <1500 meters, for every 100m increase above 1500 meters, the power is reduced by 1%
              Protection degree IP20 (higher can be customized)
              Selection table

              KLD-DVR Series Standard type

              Common model Capacity(KVA) System voltage(V) type Protection degree
              KLD-DVR100-3L-400V 100 400 Standard type NEMA1(IP20)
              KLD-DVR300-3L-400V 300 400 Standard type NEMA1(IP20)
              KLD-DVR600-3L-400V 600 400 Standard type NEMA1(IP20)
              KLD-DVR900-3L-400V 900 400 Standard type NEMA1(IP20)
              KLD-DVR1200-3L-400V 1200 400 Standard type NEMA1(IP20)
              KLD-DVR1500-3L-400V 1500 400 Standard type NEMA1(IP20)
              KLD-DVR100-4L-400V 100 400 Standard type NEMA1(IP20)
              KLD-DVR300-4L-400V 300 400 Standard type NEMA1(IP20)
              KLD-DVR600-4L-400V 600 400 Standard type NEMA1(IP20)
              KLD-DVR900-4L-400V 900 400 Standard type NEMA1(IP20)
              KLD-DVR1200-4L-400V 1200 400 Standard type NEMA1(IP20)
              KLD-DVR1500-4L-400V 1500 400 Standard type NEMA1(IP20)

              Technical Parameters


              • Input

                Rated AC input voltage:208V-480V(other voltage levels can be customized)

                Input Voltage range:-15%~+15%

                Grid frequency range:50Hz/60Hz±5Hz

                Wiring mode:Three-phase three-wire/Three-phase four-wire

                Multiple pcs in parallel:Support multi-module parallel connection

                Operating efficiency:>99%

                Output

                Compensation capability:0-100% for standard model, 100% for remaining models

                OutputFrequency:50±0.01Hz or 60±0.01Hz

                Voltage harmonic:≤3%

                Voltage imbalance (negative sequence/ positive sequence) :<3% for 100% unbalanced loads

                Overload capacity:200%

                Performance indicators

                Fast response time: <10us

                Full response time: <2ms

                Noise: ≤60db(100% load)

                Heat dissipation mode: Intelligent air cooling

                Protection functions: Short-circuit protection, DC busbar undervoltage/overvoltage protection, power semiconductor fault protection, overload protection, etc.

                Application environment

                Ambient temperature: -10℃~+50℃

                EnvironmentHumidity: Maximum 95%RH (no condensing)

                Storage temperature: -25℃~55℃

                Altitude: <1500 meters, for every 100m increase above 1500 meters, the power is reduced by 1%

                Protection degree: IP20 (higher can be customized)

              Selection table


              • KLD-DVR100-3L-400V

                Capacity(KVA):100

                System voltage(V)):400

                Type:Standard type

                Protection degree:NEMA1(IP20)

                KLD-DVR300-3L-400V

                Capacity(KVA):300

                System voltage(V)):400

                Type:Standard type

                Protection degree:NEMA1(IP20)

                KLD-DVR600-3L-400V

                Capacity(KVA):600

                System voltage(V)):400

                Type:Standard type

                Protection degree:NEMA1(IP20)

                KLD-DVR900-3L-400V

                Capacity(KVA):900

                System voltage(V)):400

                Type:Standard type

                Protection degree:NEMA1(IP20)

                KLD-DVR1200-3L-400V

                Capacity(KVA):1200

                System voltage(V)):400

                Type:Standard type

                Protection degree:NEMA1(IP20)

                KLD-DVR1500-3L-400V

                Capacity(KVA):1500

                System voltage(V)):400

                Type:Standard type

                Protection degree:NEMA1(IP20)

                KLD-DVR100-4L-400V

                Capacity(KVA):100

                System voltage(V)):400

                Type:Standard type

                Protection degree:NEMA1(IP20)

                KLD-DVR300-4L-400V

                Capacity(KVA):300

                System voltage(V)):400

                Type:Standard type

                Protection degree:NEMA1(IP20)

                KLD-DVR600-4L-400V

                Capacity(KVA):600

                System voltage(V)):400

                Type:Standard type

                Protection degree:NEMA1(IP20)

                KLD-DVR900-4L-400V

                Capacity(KVA):900

                System voltage(V)):400

                Type:Standard type

                Protection degree:NEMA1(IP20)

                KLD-DVR1200-4L-400V

                Capacity(KVA):1200

                System voltage(V)):400

                Type:Standard type

                Protection degree:NEMA1(IP20)

                KLD-DVR1500-4L-400V

                Capacity(KVA):1500

                System voltage(V)):400

                Type:Standard type

                Protection degree:NEMA1(IP20)